Why is your commercial boiler not firing? 6 common causes to check
A commercial boiler will not attempt to start for a number of reasons including, something upstream may not be calling for heat or a safety control may have shut the boiler down. Some of the more common reasons for a boiler not to attempt to start are; no call for heat, no power, gas valve closed, low water pressure, venting issues and blocked condensate drain(s) along with lockout after failed ignition attempts.
We have helped to manage many situations such as this before and whilst some of the possible reasons for no heat can be resolved in two minutes, others are safety measures that could have triggered a lockout and as such require the work of a qualified service engineer for commercial HVAC repair.
first – Safety! If you smell gas or there is a carbon monoxide alarm activation – immediately switch off and evacuate all people from the building. Then call for assistance (911 or your gas supplier’s emergency number) from outside the building.
1. Confirm There’s a Call for Heat
First check if the thermostat or a building automation system is calling for heat in the respective zone. Make sure that the schedule for that area is in ‘occupied’ mode. An Outdoor Reset control or a shutdown based on temperature for warm weather could have been activated by your controls person after last fall’s start-up.
2. Check Power and Switches
Check if the service switch for the boiler has been turned off. Also, check if the circuit breaker has tripped. Check the control display for the boiler and make sure that it is on and functioning properly. The emergency shutoff switch located on the mechanical room door can be accidentally knocked and will need to be checked as well.
3. Read the Repair History
Don’t judge a unit by one repair bill. Look at the 12-month history of repairs for the same unit and add up the total of all the repair costs. Then add the cost of the proposed repair to that number to get the real cost of repair (versus replacement).
4. Check Water Pressure and Level
Read the current pressure reading and compare to the typical reading for your boiler as recorded by your service provider. Low water pressure, or a low-water cutoff trip, will keep the boiler from attempting to fire. In investigating a low water pressure event be sure to discover the cause prior to adding water to a hot system.
5. Look at Venting and the Condensate Drain
Check for clogged condensate drain or trap – boilers will shut down if they become blocked. Look for blockages in the outdoor drain and check that all vent and air intake terminations are clear from debris such as leaves, birds’ nests etc. A fault on a pressure switch may indicate a problem with venting.
6. Read the Fault Code, Then Reset Once
First, write down the fault code displayed on the boiler’s control. Check to see if a single reset is allowed by your boiler’s manual. Most boiler manufacturers now cap the number of times a safety control can lock out a boiler before requiring a qualified service technician to attend to fix the problem. Bryan Boilers’ manual for example states: “Recontacts: 3”. If the boiler fails to light up after 3 recontacts, then a qualified service technician must attend to fix the problem.
What Not to Do
- Don’t keep pressing reset, repeated lockouts are caused by a safety control(s) that is/are doing their job.
- Do not alter or disable a safety switch, low-water switch, a pressure switch, or a limit switch.
- Boilers that have been submerged by water must be inspected by a service technician before being put into operation.
- Boilers that have been submerged by water must be inspected by a service technician before being put into operation.
- Don’t remove burner covers or adjust gas pressure.
When to Call for Commercial HVAC Repair
Compliment the service team by telling them the fault code, the things that you checked before calling for service, and how many times you had to reset the boiler before calling for service. It will save them time diagnosing the problem.
FAQ
Don’t keep trying to reset a boiler in lockout! While some of your equipment may allow you to reset the unit after a lockout, if it continues to lock out after additional tries, you need a qualified service technician to assess and fix the problem.
Is a non-firing boiler an emergency situation? Yes – in extreme temperatures near freeze, when vulnerable people are in the building and subject to the cold, and in a situation in which pipes could fail and cause damage. Read our full article on What Counts as a Commercial HVAC Emergency Service?.
Get Your Heat Back On
Morgan Mechanical has experienced commercial HVAC technicians to start up, repair and service boilers of all sizes throughout King, Snohomish, Pierce and Skagit counties. We are certified Weil-McLain installers. When winter gives way to spring and summer, we have the same staff of union electricians ready to handle all Commercial Air Conditioning Repair.
Morgan Mechanical has experienced commercial HVAC technicians to start up, repair and service boilers of all sizes throughout King, Snohomish, Pierce and Skagit counties. We are certified Weil-McLain installers. When winter gives way to spring and summer, we have the same staff of union electricians ready to handle all Commercial Air Conditioning Repair.