A Guide for Buildings located in King, Snohomish, Pierce and Skagit Counties.
Washington State Requirement for Fire Damper Inspections NFPA 80 and NFPA 105 require that all fire dampers, smoke dampers, and combination fire/smoke dampers be inspected and tested within one year of installation and then every 4 years. Hospitals are tested every 6 years. It is also required that the individual performing the test be an ICB Certified Fire Life Safety Specialist (FLSS) Fire Life Safety Level 1 or a Certified Fire and Smoke Damper Technician (CFSDT) for Fire and Smoke Dampers. Within King, Snohomish, Pierce, and Skagit Counties, local fire departments are now collecting online reports of completed fire damper tests. Reports must now be filed with the department, as simply having the reports in a binder is no longer sufficient to meet requirements.
What a fire damper does
A fire damper is typically installed in duct work that penetrates a fire rated wall, floor or ceiling. A fire damper is designed to remain open during normal ventilation operation and to close when exposed to heat. Typically a fusible link is used to open and close the damper. The fusible link melts at approximately 165°F and allows spring-loaded blades to close across the duct work to prevent the spread of flames through the barrier that was designed to protect the building.
Most commercial buildings have several types of damper:
Fire dampers (UL 555) close on heat.
Smoke dampers (UL 555S) seal upon activation of a smoke detector(s) or upon activation of the fire alarm.
Combination Fire/Smoke Dampers: Combination Fire/Smoke Dampers are designed to meet the requirements for both Fire Dampers (UL 555) and Smoke Dampers (UL 555S). Combination Dampers are typically equipped with an actuator and a heat sensor.
These special fire dampers are used to close off ceiling penetration openings passing through fire-resistive floor/ceiling assemblies and roof/ceiling assemblies.
The failure of a single damper to close when required can convert a rated wall into an unsatisfactory opening for flames in the event of a fire. Thus, a damper cannot be relied upon to function simply by visual inspection – they must be tested periodically on a schedule as mandated by the governing codes.
How often fire dampers must be inspected
Fire dampers and smoke dampers have the same inspection schedule according to NFPA 80 (fire dampers) and NFPA 105 (smoke dampers). Washington code lists the same frequency in RCW 19.27.710. Inspect all dampers owned by the building owner(s), regardless of who runs the HVAC systems.
In order to try to spread out the cost of testing all of the Fire Dampers in a commercial building, test only about 25% of the total number of dampers per year and complete testing of all of the dampers within a 4 year cycle (or 6 years for hospitals). The systems testing unit can approve a phased test schedule. Email systems testing at Seattle Fire Department (SFD) at systems_testing@seattle.gov with a complete list of all of the Fire Dampers found in the commercial building and the year in which you would like to start testing each individual damper.
Who is allowed to test fire dampers in Washington
Much of this information differs from owner’s initial perceptions regarding the fire damper testing requirements. Section 19.27.720 RCW governs the inspection and testing of fire, smoke and combination fire/smoke dampers. The person performing the inspection and testing of such devices must be a certified Fire Life Safety Specialist. The Fire Life Safety Specialist can hold one of two ICB certifications: Fire Life Safety Level 1 or Fire and Smoke Damper Technician.
Fire Life Safety Level 1, or Fire and Smoke Damper Technician
The certification program must be ANSI-accredited. General HVAC experience or certification for other types of fire protection systems will not meet the testing requirements. Ask for the certification number of each individual performing the test in the contractor’s proposal prior to entering into a contract with them.
Reporting rules by county
Different reporting procedures exist in different cities and in unincorporated county areas. Inquire with the fire marshal for the fire department that serves the building’s address as to the reporting procedures for testing fire dampers in your jurisdiction.
The Compliance Engine (TCE)
Seattle, with others in King County, expects reporting of damper tests as part of required fire system test reports since 2024, to be submitted within 7 calendar days of test for Seattle tests, for a $25 filing fee and within 10 days for Shoreline tests.
Snohomish – The Compliance Engine (TCE)
The fire system confidence reports for unincorporated areas of Snohomish County will be accepted through the TCE system. The fire prevention offices for the cities of Everett, and other Snohomish County cities, will continue to maintain fire system inspection and test records separately.
Pierce – The Compliance Engine (TCE)
Unincorporated Pierce County requires confidence testing to be entered into TCE for all fire systems since May 1, 2023. For the City of Tacoma all fire system inspection and test records are required to be entered into TCE for all commercial properties.
Skagit Tegris Fire
Skagit County commercial fire system inspections are tracked within Tegris Fire by the County. The city of Mount Vernon has its own fire marshal department separate from the County’s Fire Marshal office.
For buildings that have never had a full inventory of the dampers prior to the initial inspection by the technicians, it will take more time to complete the full inspection as they will have to locate, number and record each damper prior to testing the damper. Subsequent cycles will be easier to complete and generate reports as the inventory of the dampers will have already been completed.
What happens during a fire damper inspection
Start by locating the smoke damper. You should be able to access the individual smoke damper(s) for each section of duct work through an access door(s) located near the individual damper(s). The access door(s) should be labeled and be of sufficient size to allow adequate access to the individual damper(s).
If the necessary information about the smoke damper is marked on the fire damper, such as being a smoke damper, then the blade, frame, linkage, and sleeve are to be inspected for signs of corrosion, damage, debris, or paint. The fusible link is also to be inspected.
Remove the fusible link for the test and mark it so it can be identified for future reinstallation.
The damper is then released and a drop test is conducted to verify that the damper falls completely to shut and in the case of a latched damper, that it latches.
The fusible link is removed from the damper and reset to its original position as required by NFPA 80. Note that a new link is not required to be installed at every test.
For “Cycle Powered” dampers (Smoking, Combination) ensure they Cycle open & close from their control or the fire alarm signal.
Documenting your findings. As the technician conducting the inspection you need to record the Damper Number, Location, Result, Photos etc. and any action required to put the damper back into full working order.
As outlined in NFPA 80 and 105, there are a few damper(s) that are exempt from having to be inspected because they cannot be reached. These should be noted and indicated on the reports as being exempt with a reason for why they are unable to be reached.
Common problems we find
Cables, conduit or sprinkler pipes passing through the damper opening and thereby preventing the blades from closing.
Missing, blocked or painted-over access doors
Painted or corroded fusible links, or links with the wrong temperature rating
Blades are jammed by debris (brass, duct, insulation), are stuck due to a bent damper frame or are blocked by insulation.
Dampers removed or disconnected during a remodel and never put back.
Smoke dampers that don’t respond to the fire alarm signal
They are defects in the means to prevent fire to spread through your building. Each deficiency must be repaired or a plan to repair must exist when the local fire department performs their inspection of your building. The current state deadline for correcting deficiencies should be confirmed with the local fire marshal before a number of months is stated.
How to prepare for an inspection
Assess your existing conditions based upon the mechanical drawings of your facility and prior damper inspections conducted of your fire dampers.
Plan for access to ceilings in all spaces (e.g. tenant spaces, server rooms, secure areas).
Determine the best time for Morgan Mechanical to shut down your HVAC systems for the inspection and testing of your smoke or combination dampers and have your fire alarm vendor attend as necessary.
Budgeting for repairs. Morgan Mechanical has seen a variety of missing access doors and untested (or never installed) dampers in older buildings.
Schedule damper testing with your scheduled HVAC preventive maintenance and have one contractor complete the testing for you.
Fire damper inspection with Morgan Mechanical
Morgan Mechanical is a union mechanical contractor located in Redmond, WA. We service commercial buildings throughout King, Snohomish, Pierce and Skagit Counties with fire, smoke and combination damper inspection, testing, repair and replacement by our [ICB-certified] technicians. We maintain an inventory of parts for the various types of dampers and can have them shipped to your location within 24-48 hours. We also file the reports for the various cities and counties for fire damper testing through The Compliance Engine for counties that require it such as Seattle, many King County cities, Tacoma and unincorporated Pierce and Snohomish Counties. For Skagit County jobs we file reports through Tegris.